Product Overview
The KYN61-40.5 metal-clad withdrawable switchgear supports power receiving, distribution, circuit control and protection in 35kV electrical networks.
Its compartmentalized construction and withdrawable design support organized equipment arrangements and convenient maintenance.
Incoming & Outgoing Circuits
Flexible feeder and busbar arrangements.
Protection & Control
Relay protection, metering and control.
Installation & Maintenance
Convenient inspection and service access.
Technical Specifications
1. Switchgear Technical Parameters
| Parameter | Unit | Specification |
| Rated Voltage | kV | 40.5 |
| Rated Current | A | 1250 / 1600 / 2000 |
| Rated Frequency | Hz | 50 |
| Rated Short-Time Withstand Current (4s) | kA | 20 / 25 / 31.5 |
| Rated Peak Withstand Current | kA | 50 / 63 / 80 |
| Power-Frequency Withstand Voltage (1 min) | kV | 95 |
| Lightning Impulse Withstand Voltage | kV | 185 |
| Degree of Protection | — | Enclosure IP3X; Compartments IP2X |
2. Vacuum Circuit Breaker Technical Parameters
| Parameter | Unit | Specification |
| Rated Voltage | kV | 40.5 |
| Rated Frequency | Hz | 50 |
| Power-Frequency Withstand Voltage (1 min) | kV | 95 |
| Lightning Impulse Withstand Voltage | kV | 185 |
| Rated Current | A | 1250 / 1600 / 2000 |
| Rated Short-Time Withstand Current | kA | 20 / 25 / 31.5 |
| Rated Short-Circuit Breaking Current | kA | 20 / 25 / 31.5 |
| Rated Peak Withstand Current | kA | 50 / 63 / 80 |
| Rated Short-Circuit Duration | s | 4 |
| Opening Time | ms | 30–60 |
| Closing Time | ms | 50–100 |
| Rated Short-Circuit Breaking Operations | Times | 20 |
| Mechanical Life | Times | 10,000 |
| Rated Operating Sequence | — | O–0.3s–CO–180s–CO |
3. Spring Operating Mechanism Technical Parameters
| Parameter | Unit | Specification |
| Rated Operating Voltage – Opening Coil | V | DC 220/110; AC 220/110 |
| Rated Operating Voltage – Closing Coil | V | DC 220/110; AC 220/110 |
| Rated Operating Current – Opening Coil | A | 0.96 (220V); 1.05 (110V) |
| Rated Operating Current – Closing Coil | A | Not specified |
| Energy-Storage Motor Power | W | 230 |
| Rated Voltage of Energy-Storage Motor | V | DC 220/110; AC 220/110 |
| Energy-Storage Time | s | ≤ 12 |
Switchgear Structure & Components
The KYN61-40.5 features a compartmentalized metal-clad structure with separate sections for circuit breakers, busbars, cable connections, and protection equipment.

Applications
Utilities and industrial facilities use KYN61-40.5 metal-clad switchgear to distribute power and provide control and protection in 35 kV-class electrical systems.

Utility Substations
Incoming and outgoing feeders in 35kV substations.

Industrial Facilities
Power distribution for large industrial plants.

Power Generation
Switching and protection for plant electrical systems.

Mining Operations
Electrical distribution for mining facilities.

Renewable Energy
Collector substations for solar and wind projects.

Infrastructure Projects
Power supply for large infrastructure facilities.
Features & Benefits
KYN61-40.5 switchgear combines vacuum circuit breaker technology with a spring operating mechanism to meet different electrical rating and control requirements.
Manufacturing Capabilities
Our manufacturing process covers sheet metal fabrication, equipment assembly, electrical wiring and final inspection. Each production stage follows approved technical drawings and project requirements.

01. Sheet Metal Fabrication
Cabinet panels and structural parts are processed to meet specified dimensions and design requirements.

02. Equipment Assembly
Switchgear compartments and electrical components are assembled according to approved configurations.

03. Electrical Assembly
Control, protection and auxiliary circuits are wired according to project diagrams.

04. Quality Inspection & Testing
Applicable inspections and electrical tests are performed according to project requirements.
Certifications & Compliance
F A Q s
35kV refers to the nominal system voltage, while 40.5kV is the equipment rated voltage.
The supplied specification lists 1250A, 1600A and 2000A.
20kA, 25kA and 31.5kA for 4 seconds.
Available documentation should be confirmed for the specific project configuration.